Switching Relay Provides Dpst Switching For Hydronic Zone Controlled Heating Systems Or Spst Control Of Two Separate Loads. The R845A May Be Directly Controlled By Any 2-Wire Series 80 Thermostat.
Description
Switching Relay With Internal Transformer, Provides Dpst Switching For Hot Water Zone Control Systems, Or Spst Control Of Two Separate Loads.
Application
- Provide Intermediate Switching Of A Line Voltage Device Form A Low Voltage Controller.
- Switching Action Dpst
- One Pole Line Voltage, The Other Line Or Low Voltage Coil Ratings
- Current 0.4A
- Coil Ratings Voltage, 24 Vac
- Transformer Primary Rating, 120 Vac, 50/60 Hz
- Transformer Secondary Rating, 24 Vac
- Temperature Range (F): 115 F Maximum Ambient For 60 Hz. 105 F Max. Ambient For 50 Hz.
- Temperature Range (C) 46 C Maximum Ambient For 60 Hz. 41 C Maximum Ambient For 50 Hz.
- Thermostat Compatibility: Low Voltage (Class 2) 2-Wire
- Dimensions (In.) 5-1/4″ High X 4-1/4″ Wide X 2-5/16″ Deep
- Dimensions (Mm) 133 Mm High X 108 Mm Wide X 59 Mm Deep
- Electrical Ratings – Primary Voltage 120V. 50/60 Hz
- Electrical Connections (Control Circuit) 2-Wire
- Approvals, Underwriters Laboratories Inc,Listed: File No. E4436, Guide No. Xapx
- Approvals, Canadian Standards Association, Certified: File No. Lr1620
- Includes Integral Transformer, Enclosure
- Tradeline Value: Tradeline
- Electrical Ratings (Maximum Input) 5.0 W
- Electrical Ratings (Primary Voltage) 120V, 50/60 Hz
- Contacts Electrical Rating Main Contacts 120 Vac: 7.4A Afl. 44.4A Alr. 10A Resistive
- Contacts Electrical Rating Secondary Contacts 120 Vac: 3A Alf. 18A Alr
- Contacts Electrical Rating Main Contacts 240 Vac: 3.7A Alf. 22.2A Alr. 6.0A Resistive
- Contacts Electrical Rating Secondary Contacts 240 Vac: 2A Afl. 12A Alr
- Contacts Electrical Rating Secondary Contacts Pilot Duty Rat 50 Va @ 24V
- Contacts Electrical Rating Contacts Max. Connected Load 2000 Va (120 Vac To 240 Vac)
- Electrical Rating: Maximum Input 5.0W
Reviews