The P28 And P128 Series Lube Oil Controls Provide Dependable And Economical Oil Pressure Cut-Out Forpressure-Lubricated Refrigeration Compressors. The Field-Adjustable Pressure Differential Of These Controlsprovides Compressor Operation According To The Manufacturer?S Specifications. The P28 And P128Controls Operate By Measuring The Net Lube Oil Pressure And De-Energizing The Compressor If The Pressure Falls Below The Differential Setpoint.
Manual Or Automatic Reset Models Are Available With Factory Set And Sealed Time Delays Of 30, 45, 60, 90,Or 120 Seconds (All Time Delays May Not Be Available On All Models). The P128 Is The Same Control As Thep28 But With 1/4 Inch Male Flare Pressure Connections.
Features And Benefits
- Built-In Time Delay Relaywith Ambient Compensation: Minimizes Timing Fluctuations Due To Temperature Variations
- Trip-Free Manual Reset: Provides Manual Reset That Cannot Be Overridden By Pressing And Holding The Reset Button
- Replaceable Time Delay Relay Assembly: Allows Easy Field Replacement Of The Time Delayrelay And Terminal Board
- Available With Runlight And Alarm Terminals:Allows The Control To Be Wired For Normal Oil Pressure Runlight Signals And Shutdown Alarm Circuits For Remote Monitoring Of Oil Pressure Status
Specifications
- Adjustable Cut-Out Pressure Difference: 8 To 70 Psi
- Maximum Differential: 70 Psi
- Maximum Working Pressure: 250 Psig (On The High Side)
- Maximum Overpressure: 325 Psi (Oil And Low Side Pressure)
- The Time Delay Relay Is De-Energized 3 To 5 Psi (21 To 34 Kpa) Above The Cut-Out Scale Setting.
- Pressure Switch Units: Enclosed Dust-Protected Pennswitch
- Ambient Operating Conditions: 32 To 104?F / 0 To 40?C
- Mounting: Flat Surface Or With A Universal Mounting Bracket (Part No. 271-51)
- Wiring Terminal: Large 8-32 X 1/4 In. Binder Head Screws
- Dimensions: 5.66 X 5.32 X 2.09 In. / 144 X 135 X 53 Mm