Provides Automatic, Nonrecycling Control Of An Intermittent Ignition Oil Burner System.
Features:
- Description: Protectorelay Oil Burner Control With 45 Seconds Lock Out Timing
- Ignition Type: Intermittent
- Timing, Safety Switch: 45 Sec.
- Mounting Bracket: For Mounting On A Standard 4 In. X 4 In. Junction Box Or Direct Mounting On Burner Housing.
- Electrical Ratings (Full Load): 7.4 A @ 120 Vac; 3.7 A @ 240 Vac
- Electrical Ratings (Locked Rotor): 44.4 A @ 120 Vac; 22.2 A @ 240 Vac
- Alarm Load Ratings (Pilot Duty): 75 Va @ 120/240 Vac, 50-60 Hz; 25 Va @ 24V, 50-60 Hz
- Alarm Load Ratings (Resistive): 1.5 A @ 120/240V, 50-60Hz; 3 A @ 24 V, 50-60 Hz
- Dimensions: 4 3/8 In. High X 4 1/8 In. Wide X 2 1/2 In. Deep
- Temperature Range: -40 F To +130 F
- Comments: With Led For Lockout Indication, And Manual Trip Lever On Safety Switch To Assure Burner Shutdown During Servicing.
Specifications:
- Controls Oil Burner, Oil Valve (If Desired) And The Ignition Transformer In Response To A Call For Heat.
- Solid State Flame Sensing Circuit.
- Led On Terminal Strip Indicates System Lockout.
- Remote Lockout Indication Available On Some Models.
- Enclosed Safety Switch With External Reset Button.
- Manual Trip Lever Opens Safety Switch For System Maintenance.
- Mounts On Standard 4 X 4 In. Junction Box; Select Models May Be Mounted Directly On Burner Housing.
- C554A Cadmium Sulfide Flame Detector And 24 Vac Thermostat Required.
Reviews
There are no reviews yet.